80mm Cast Iron PN16 Type 2 Fire Hydrant The PN16 fire hydrant is designed for connection to large diameter mains for industrial purposes where the watermain is buried deep underground. Built from strong, robust ductile iron, the hydrant meets BS750 Type 2 specification. Offering minimum head loss, the valve cuts off when in an open position to ensure least possible restriction into the flow path. The rigid bolted bonnet construction makes It very secure and easy to dismantle with one wrench.
Summary: - Fully maintainable - Exceeds flow requirements - Automatic frost drain valve as standard - Low weight, compact design - 16.1kg for easy handling and installation - Corrosion resistant - WRAS approved - Available with fixed or loose stopper Specifications: Body Ductile Iron
Tests Hydraulic test to BS 750 Seat 1.1 x PN Body 1.5 x PN Operating torque test
Maximum Working Pressure 16 Bar
Temperature Range - 10°C to + 60°C (insulation essential for temperatures of 0°C and below)
Options: Stainless steel (standard) or Gunmetal to BS750 round thread Instantaneous (Morris) Belfast London "V" thread Internal screwed Norwegian Bayonet (Dublin)
Applicable standards: Inlet flange universally drilled for connections to BS EN 1092-2 PN 10/16 and to BS 10 Table D/E Fully compliant to BS EN 14339 in respect of construction Product Directive (CPD) 89/106/EEC,BS EN 1074-6 and BS 750